Flow monitoring instrument TU 7050
Complete monitoring - safely!
Switching transmitter for Turbotron flow sensors - Remote mount version
The TU 7050 is a two channel switching transmitter for use with all Turbotron Series flow sensors.
Pulse signals from flow sensors operate a dual set of galvanically insulated, dry contacts which in turn, may be used to activate alarms.
Set point adjustments are allowed, in up to 16 increments, via a pair of rotary switches set into the module’s front panel.
The rear panel contains the DIN rail mounting assembly.
Two selectable modes are available:
Mode A
Two identical turbine flow sensors operate one set point each.
Mode B
One turbine flow sensor operates a pair of alarm set points
(pre-alarm & main alarm or min & max).
Signal input
Frequency signals of up to two identical flow sensors
VT...15
VT...25
VT...40
Set point range
VT...15 0,5...29,5 l/min
VT...25 3...100 l/min
VT...40 7...275 l/min
Outputs
Two independent, potential free c/o contacts